TDK Lambda | Z+Low Voltage User Manual
Global Commands List
Result From Supply
Command Name
Description
SCPI Format
GEN Format
Enable all Outputs Output On to last V & I levels Disable all Outputs Turn outputs Off to zero V & I Program all Voltages Set all power supply output voltage Program all Currents Set all power supply output current
GLOBal:OUTPut:STATe 1|ON
GOUT 1
None
GLOBal:OUTPut:STATe 0|OFF
GOUT 0
None
GLOBal:VOLTage:[AMPLitude] xxx.yy GPV xxx.yy
None
GLOBal:CURRent:[AMPLitude] xxx.yy GPC xxx.yy
None
Save Settings of all power supplies Recall Settings of all power supplies Reset all supplies
Same as *SAV n
GLOBal:*SAV
GSAV n
None
Same as *RCL n
GLOBal:*RCL
GRCL n
None
Same as *RST
GLOBal:*RST
GRST
None
Table 7-12: Global Commands
7.13 Command Summary Common Commands
SCPI Command
Description
GEN Command
*CLS
Clear status
CLS
*ESE
Standard event status enable
*ESE? *ESR? *IDN? *OPC *OPC? *OPT?
Return standard event status enable
Return event status register
Return instrument identification string Set ”operation complete” bit in ESR
IDN?
Return a ”1”when operation command complete
Return option number
*PSC {1|0}
Power - ON status enable (1) /disable (0)
*PSC?
Power - ON status clear
*RCL {1|2|3|4}
Recalls a saved instrument state
RCL RST SAV
*RST
Reset
*SAV {1|2|3|4} *SRE
Saves an instrument state
Set service request enable register Return service request enable register
*SRE? *STB? *TRG
Return status byte
Trigger
115
Made with FlippingBook Annual report maker