Table 4-3.1 system check list (continue):
DSP1 content
Parameters displayed on DSP2
Remarks
34.--
EEVD position
Actual value = value displayed × 4
35. --
Compressor discharge pressure(MPa)
Actual value = value displayed × 0.01
36. --
Compressor suction pressure (MPa)
Actual value = value displayed × 0.01
37. --
Number of indoor units online
Actual value = value displayed (1)
38.--
Number of indoor units operating
Actual value = value displayed (1)
39. --
Heat exchanger status(outdoor unit)
0: OFF, 1: C1- Cooling mode, 2: D1- Disabled (Cooling mode) (4) , 3: D2- Compressor OFF (Cooling mode), 4: E1- Heating mode, 5: F1- Disabled (Heating mode), 6: F2- Compressor OFF (Heating mode)
0: No special mode, 1: oil Return, 2: Defrost, 3: Start-up, 4: Stop, 5: Quick Check, 6: Self cleaning
40.--
Special state
41. --
Silent mode
0~14 ,14 represents the most silent
42.--
Static pressure mode
0: 0Pa, 1: 20Pa, 2: 40Pa, 3: 60Pa, 4: 80Pa, 5: 100Pa, 6: 120Pa
43.--
Tes (°C)
Actual value = value displayed (5)
43.--
Tcs (°C)
Actual value = value displayed (5)
45.--
DC Voltage(V)
Actual value = value displayed
46.--
AC Voltage(V)
Actual value = value displayed
47.---
Number of cooling mode IDUs
Actual value = value displayed
48.--
Number of heating mode IDUs
Actual value = value displayed
49.--
Capacityof cooling mode IDUs (HP)
Actual value = value displayed
50.--
Capacityof heating mode IDUs (HP)
Actual value = value displayed
51 .--
Refrigerant volume judgment
Refer to Note 7
52.---
Dirty blockage rate
0~10, 10 represents the worst
53.--
Fan error
54.---
Software version
55.--
Last error code
-- --
--
End