אלקטרה VRF | קטלוג טכני 2025
142
קריאת פרמטרים Up-Down לקריאת פרמטרים דרך צג המעבה יש להיעזר בלחצני
Table 4-3.1 system check list:
DSP1 conten t
Parameters displayed on DSP2
Remarks
--.--
"Standby (ODU address+ IDU number)/frequency/special status"
Master unit: 0; slave units: 1, 2 255 represents invalid address.
0.--
Outdoor unit address
1. --
Outdoor unit capacity
Actual value = value displayed (HP)
2.--
Number of outdoor units
1~4 (1)
3.--
Number of indoor units set
1~64 (1)
4.--
Total capacity of outdoor unit
Only available for master unit (2)
5.--
Target frequency of this ODU
Displacement frequency (3)
6.--
Target frequency of ODU system
Target frequency= value displayed ×10
7. --
Inverter compressor A actual frequency (Hz)
Actual value = value displayed
8.--
Inverter compressor B actual frequency (Hz)
Actual value = value displayed
9.--
Operating mode
0: OFF, 2: Cooling, 3: Heating, 5: main cooling (4) , 6: main heating (4)
10.--
Fan A speed index(rpm)
Actual value = value displayed
11 .--
Fan Bspeed index (rpm)
Actual value = value displayed
12.--
Indoor heat exchanger pipe (T2) averagetemperature (°C)
Actual value = value displayed
13.--
Indoor heat exchanger pipe (T2B) averagetemperature (°C)
Actual value = value displayed
14.--
Main heat exchanger pipe (T3) temperature (°C)
Actual value = value displayed
15.--
Outdoor ambient (T4) temperature (°C)
Actual value = value displayed
16.--
Liquid pipe (T5) temperature (°C)
Actual value = value displayed
17.--
Microchannel heat exchangerinlet pipe (T6A) temperature (°C)
Actual value = value displayed
18.--
Microchannel heat exchanger outlet pipe (T6B) temperature (°C)
Actual value = value displayed
19.--
Inverter compressor A discharge (T7C1) temperature (°C)
Actual value = value displayed
20.--
Inverter compressor B discharge (T7C2) temperature (°C)
Actual value = value displayed
21 .--
Inverter compressor A suction (T71) temperature (°C)
Actual value = value displayed
22.--
Inverter compressor B suction (T72) temperature (°C)
Actual value = value displayed
23.--
(T8) temperature (°C)
Actual value = value displayed
24.--
Inverter module heatsink (Ntc)temperature (°C)
Actual value = value displayed
25.--
Reserved for heat recovery unit ’s T9 temperature (°C)
Actual value = value displayed
26.--
Outdoor heat exchanger liquid (TL)temperature (°C)
Actual value = value displayed
27.--
Discharge superheat degree (°C)
Actual value = value displayed
28.--
Primary current (A)
Actual value = value displayed /10
29.--
Inverter compressor A current (A)
Actual value = value displayed /10
30.--
Inverter compressor A current (A)
Actual value = value displayed /10
31. --
EXVA position
Actual value = value displayed × 24
32.--
EEVB position
Actual value = value displayed × 24
33. --
EEVC position
Actual value = value displayed × 4
Made with FlippingBook - Online Brochure Maker