אלקטרה VRF | קטלוג טכני 2025

142

קריאת פרמטרים Up-Down לקריאת פרמטרים דרך צג המעבה יש להיעזר בלחצני

Table 4-3.1 system check list:

DSP1 conten t

Parameters displayed on DSP2

Remarks

--.--

"Standby (ODU address+ IDU number)/frequency/special status"

Master unit: 0; slave units: 1, 2 255 represents invalid address.

0.--

Outdoor unit address

1. --

Outdoor unit capacity

Actual value = value displayed (HP)

2.--

Number of outdoor units

1~4 (1)

3.--

Number of indoor units set

1~64 (1)

4.--

Total capacity of outdoor unit

Only available for master unit (2)

5.--

Target frequency of this ODU

Displacement frequency (3)

6.--

Target frequency of ODU system

Target frequency= value displayed ×10

7. --

Inverter compressor A actual frequency (Hz)

Actual value = value displayed

8.--

Inverter compressor B actual frequency (Hz)

Actual value = value displayed

9.--

Operating mode

0: OFF, 2: Cooling, 3: Heating, 5: main cooling (4) , 6: main heating (4)

10.--

Fan A speed index(rpm)

Actual value = value displayed

11 .--

Fan Bspeed index (rpm)

Actual value = value displayed

12.--

Indoor heat exchanger pipe (T2) averagetemperature (°C)

Actual value = value displayed

13.--

Indoor heat exchanger pipe (T2B) averagetemperature (°C)

Actual value = value displayed

14.--

Main heat exchanger pipe (T3) temperature (°C)

Actual value = value displayed

15.--

Outdoor ambient (T4) temperature (°C)

Actual value = value displayed

16.--

Liquid pipe (T5) temperature (°C)

Actual value = value displayed

17.--

Microchannel heat exchangerinlet pipe (T6A) temperature (°C)

Actual value = value displayed

18.--

Microchannel heat exchanger outlet pipe (T6B) temperature (°C)

Actual value = value displayed

19.--

Inverter compressor A discharge (T7C1) temperature (°C)

Actual value = value displayed

20.--

Inverter compressor B discharge (T7C2) temperature (°C)

Actual value = value displayed

21 .--

Inverter compressor A suction (T71) temperature (°C)

Actual value = value displayed

22.--

Inverter compressor B suction (T72) temperature (°C)

Actual value = value displayed

23.--

(T8) temperature (°C)

Actual value = value displayed

24.--

Inverter module heatsink (Ntc)temperature (°C)

Actual value = value displayed

25.--

Reserved for heat recovery unit ’s T9 temperature (°C)

Actual value = value displayed

26.--

Outdoor heat exchanger liquid (TL)temperature (°C)

Actual value = value displayed

27.--

Discharge superheat degree (°C)

Actual value = value displayed

28.--

Primary current (A)

Actual value = value displayed /10

29.--

Inverter compressor A current (A)

Actual value = value displayed /10

30.--

Inverter compressor A current (A)

Actual value = value displayed /10

31. --

EXVA position

Actual value = value displayed × 24

32.--

EEVB position

Actual value = value displayed × 24

33. --

EEVC position

Actual value = value displayed × 4