ELECTRA | FAN COILS CATALOG 2024
AWS 4000
1700
1640
20
103
850
1/8”
Left
ø2
Right
AIR SUPPLY
ø2”
AIR Return
1 /8”
345
666
ø2
790
221
221
400
400
ø2”
30
580 x 1520
AIR SUPPLY
1700
790
Technical Data
Dimensions in mm.
Sound pressure level*
Air flow rate
6800 (4000) 2 x DD 12-12 3 /1 (x2) 910 220-240/1/50 3.9 (x2)
dBA H -55 M -53 L -51
M 3 /HR (CFM):
Fan quantity/type Fan motor
External static pressure Inch H 2 O: Drain tube diameter Inch: Fuse (Type) A(C): Coil face area Ft 2 /m 2 : Weight (Net) Kg:
0.25 (8 rows) 1-1/8 16 8.8 / 0.82 150
SPEED/ HP:
Nominal rpm Power supply
V/PH/Hz:
Current
A:
Shut-off Valve
Electric Heater Options
Inch:
1-1/4 BSP
22.5 3x50
kW:
15 3x32
7.5
Fuse Protection
* Sound pressure level measured at 1.8 m' from unit side and 1.5m' above floor level Extra insulation 1 inch and perforated sheet metal on the side panels reduces the sound level up to 2 DB.
A:
3x20
Water cooling coil rating (8-rows)
EAT (F)
85 DB 71 WB
95 DB 78 WB
EWT WTR
TC
SC
FLOW PD
TC
SC
FLOW PD
ºF
ºF
kbtuh kbtuh gpm ft
kbtuh kbtuh gpm ft
8
273.9
161.1
68.0
9.0
394.5
206.0
98.4
17.8
42
10
252.4
151.7
50.1
5.0
374.1
197.2
74.6
10.6
12
227.7
141.4
37.8
3.0
348.4
187.7
57.9
6.6
8
244.0
148.2
60.8
7.2
364.3
192.9
90.8
15.3
221.5
138.8
44.2
4.0
339.7
183.9
67.7
8.7
45
10
194.6
128.0
32.3
2.2
319.5
175.1
53.0
5.6
12
212.0
135.0
52.8
5.5
332.1
179.8
82.6
12.7
8
189.2
125.9
37.7
2.9
309.4
171.1
61.7
7.3
48
10
162.1
115.3
26.9
1.6
284.8
162.0
47.3
4.4
12
For any coils options water rating according to AW 4000 Model.
Valve Options
ON/OFF
Propotional
2Way -1 3Way-1 1 /4 1 /4
2Way -1 3Way-1 1 /4 1 /4
Valve Cooling
ON/OFF Propotional Valve 2Way -3/4 3Way-3/4 2Way -3/4 3Way-3/4 Heating
Kvs - Amount of flow
Preliminary data Specifications subject to change without notice
EA - Entering Air Temperature ˚F EWT - Entering Water Temperature ˚F WTR - Water Temperature Rise ˚F
TC - T OTAL #OOLING #APACITY IN s BTU/H SC - 3ENSIBLE #OOLING #APACITY IN s BTU/H PD - Pressure Drop FT H2O
46
41