ELECTRA | FAN COILS CATALOG 2024

AWS 3500

1700

1640

20

103

850

1/8”

Left

ø2

Right

AIR SUPPLY

ø2”

AIR Return

1 /8”

345

666

ø2

790

221

221

400

400

ø2”

30

580 x 1520

AIR SUPPLY

1700

790

Technical Data

Dimensions in mm.

Sound pressure level*

Air flow rate

dBA H -55 M -53 L -51

5950 (3500) 2 x DD 12-12 3 /1 (x2) 910 220-240/1/50 3.9 (x2)

M 3 /HR (CFM):

Fan quantity/type Fan motor

External static pressure Inch H 2 O: Drain tube diameter Inch: Fuse (Type) A(C): Coil face area Ft 2 /m 2 : Weight (Net) Kg:

0.25 (8 rows) 1-1/8 16 8.8 / 0.82 150

SPEED/ HP:

Nominal rpm Power supply

V/PH/Hz:

Current

A:

Shut-off Valve

Electric Heater Options

Inch:

1-1/4 BSP

22.5 3x50

kW:

15 3x32

7.5

Fuse Protection

* Sound pressure level measured at 1.8 m' from unit side and 1.5m' above floor level Extra insulation 1 inch and perforated sheet metal on the side panels reduces the sound level up to 2 DB.

A:

3x20

Water cooling coil rating (8-rows)

EAT (F)

85 DB 71 WB

95 DB 78 WB

EWT WTR

TC

SC

FLOW PD

TC

SC

FLOW PD

ºF

ºF

kbtuh kbtuh gpm ft

kbtuh kbtuh gpm ft

8

246.6

144.4

61.3

7.3

355.8

185.1

88.7

14.7

42

10

227.6

136.0

45.3

4.2

337.0

176.9

67.2

8.7

12

204.4

204.4

33.9

2.4

313.2

167.9

52.1

5.4

8

219.6

132.5

54.4

5.8

328.9

173.3

81.9

12.4

199.9

124.3

39.7

3.3

306.0

164.8

61.0

7.2

45

10

174.5

114.0

28.9

1.9

288.4

156.9

59.8

4.7

12

191.4

120.9

47.6

4.5

295.2

160.3

73.3

10.1

8

169.5

112.1

33.7

2.4

279.3

153.4

55.6

6.1

48

10

145.0

102.6

24.1

1.3

257.3

145.2

42.7

3.7

12

For any coils options water rating according to AW 3500 Model.

Valve Options

ON/OFF

Propotional

2Way -1 3Way-1 1 /4 1 /4

2Way -1 3Way-1 1 /4 1 /4

Valve Cooling

ON/OFF Propotional Valve 2Way -3/4 3Way-3/4 2Way -3/4 3Way-3/4 Heating

Kvs - Amount of flow

Preliminary data Specifications subject to change without notice

EA - Entering Air Temperature ˚F EWT - Entering Water Temperature ˚F WTR - Water Temperature Rise ˚F

TC - T OTAL #OOLING #APACITY IN s BTU/H SC - 3ENSIBLE #OOLING #APACITY IN s BTU/H PD - Pressure Drop FT H2O

45