ELECTRA | FAN COILS CATALOG 2024
AWS 3500
1700
1640
20
103
850
1/8”
Left
ø2
Right
AIR SUPPLY
ø2”
AIR Return
1 /8”
345
666
ø2
790
221
221
400
400
ø2”
30
580 x 1520
AIR SUPPLY
1700
790
Technical Data
Dimensions in mm.
Sound pressure level*
Air flow rate
dBA H -55 M -53 L -51
5950 (3500) 2 x DD 12-12 3 /1 (x2) 910 220-240/1/50 3.9 (x2)
M 3 /HR (CFM):
Fan quantity/type Fan motor
External static pressure Inch H 2 O: Drain tube diameter Inch: Fuse (Type) A(C): Coil face area Ft 2 /m 2 : Weight (Net) Kg:
0.25 (8 rows) 1-1/8 16 8.8 / 0.82 150
SPEED/ HP:
Nominal rpm Power supply
V/PH/Hz:
Current
A:
Shut-off Valve
Electric Heater Options
Inch:
1-1/4 BSP
22.5 3x50
kW:
15 3x32
7.5
Fuse Protection
* Sound pressure level measured at 1.8 m' from unit side and 1.5m' above floor level Extra insulation 1 inch and perforated sheet metal on the side panels reduces the sound level up to 2 DB.
A:
3x20
Water cooling coil rating (8-rows)
EAT (F)
85 DB 71 WB
95 DB 78 WB
EWT WTR
TC
SC
FLOW PD
TC
SC
FLOW PD
ºF
ºF
kbtuh kbtuh gpm ft
kbtuh kbtuh gpm ft
8
246.6
144.4
61.3
7.3
355.8
185.1
88.7
14.7
42
10
227.6
136.0
45.3
4.2
337.0
176.9
67.2
8.7
12
204.4
204.4
33.9
2.4
313.2
167.9
52.1
5.4
8
219.6
132.5
54.4
5.8
328.9
173.3
81.9
12.4
199.9
124.3
39.7
3.3
306.0
164.8
61.0
7.2
45
10
174.5
114.0
28.9
1.9
288.4
156.9
59.8
4.7
12
191.4
120.9
47.6
4.5
295.2
160.3
73.3
10.1
8
169.5
112.1
33.7
2.4
279.3
153.4
55.6
6.1
48
10
145.0
102.6
24.1
1.3
257.3
145.2
42.7
3.7
12
For any coils options water rating according to AW 3500 Model.
Valve Options
ON/OFF
Propotional
2Way -1 3Way-1 1 /4 1 /4
2Way -1 3Way-1 1 /4 1 /4
Valve Cooling
ON/OFF Propotional Valve 2Way -3/4 3Way-3/4 2Way -3/4 3Way-3/4 Heating
Kvs - Amount of flow
Preliminary data Specifications subject to change without notice
EA - Entering Air Temperature ˚F EWT - Entering Water Temperature ˚F WTR - Water Temperature Rise ˚F
TC - T OTAL #OOLING #APACITY IN s BTU/H SC - 3ENSIBLE #OOLING #APACITY IN s BTU/H PD - Pressure Drop FT H2O
45
40