TDK Lambda | Z+High Voltage User Manual
3.9.9 Connecting Multiple Loads, Radial Distribution Method Fig.3-8 shows multiple loads connected to one supply. Each load should be connected to the power supply’s output terminals using separate pairs of wires. It is recommended that each pair of wires will be as short as possible and twisted or shielded tominimize noise pick-up and radiation. The sense wires should be connected to the power supply output terminals or to the load with the most critical load regulation requirement.
Load lines, twisted pair, shortest length possible.
+V -V
+ - + -
Load#1
Power Supply
Load#2
-Rem. sense -Local sense +Rem. sense +Local sense
+ -
Load#3
Fig.3-8: Multiple loads connection, radial distribution, local sense
3.9.10 Multiple Load Connection with Distribution Terminals If remotely located output distribution terminals are used, the power supply output terminals should be connected to the distribution terminals by a pair of twisted and/or shieldedwires. Each load should be separately connected to the remote distribution terminals (see Fig.3-9). If remote sensing is required, the sensingwires should be connected to the distribution terminals or at the most critical load.
Distribution terminal
+V -V
+ - + -
Load#1
+V
Power Supply
Load#2
-Rem. sense -Local sense +Rem. sense +Local sense
+ -
-V
Load#3
Fig.3-9: Multiple loads connection with distribution terminal
44
Made with FlippingBook - professional solution for displaying marketing and sales documents online