TDK Lambda | Z+High Voltage User Manual
Model 160-1.3 320-0.65 650-0.32
Minimum (A)
Maximum (A)
Model
Minimum (A)
Maximum (A)
0.00000 0.00000 0.00000
1.30000 0.65000 0.32000
160-2.6 320-1.3 650-0.64
0.00000 0.00000 0.00000
2.60000 1.30000 0.64000
Table 7-6: Z200 models Current programming range and communication response format
Table 7-7: Z400 models Current programming range and communication response format
NOTE: Thepower supply canaccept values higher by5%than the tablevalues, however it is not recommended to program the power supply over the rated values.
Model Rated Output Voltage (V)
Model Rated Output Voltage (V)
Minimum (V) Maximum (V)
Minimum (V) Maximum (V)
160 320 650
5 5 5
176 353 717
160 320 650
0 0 0
152 304
617.5
Table 7-9: OVP programming range and communication response format
Table 7-10: UVL/UVP programming range and communication response format
NOTE: The UVP protection starts operating for values higher than 5% of Rated Output Voltage.
90