TDK Lambda | Z+Low Voltage User Manual
3.9.2 Current Carrying Capacity Two factors must be considered when selecting the wire size:
1. Wires should be at least heavy enough not to overheat while carrying the power supply load current at the rated load, or the current that would flow in the event the load wires were shorted, whichever is greater. 2. Wire size should be selected to enable voltage drop per lead to be less than 1.0V at the rated current. Although units will compensate higher voltage drop in each load wire (refer to the specifications). It is recommended to minimize the voltage drop (1V maximum) to prevent excessive output power consumption from the power supply and poor dynamic response to load changes. Please refer to Tables 3-2 and 3-3 for maximum wire length to limit voltage drop in American and European dimensions respectively.
Wire size AWG
Resistivity Ohm/1000ft
Maximum length in feet to limit voltage drop to 1V or less 5A 10A
20A
50A
80A
14 12 10
2.526 1.589
80
40 60
20 30 50 80
8
5
120 200 320 500 800
12 20 32 50 80
7.5
0.9994 0.6285 0.3953 0.2486 0.1564
100 160 250 400 600
12.5
8 6 4 2
20 31 50 78
125 200 300
1200
125
Table 3-2: Maximum wire length for 1V drop on lead (in feet)
Cross sect. area (mm 2 )
Resistivity Ohm/Km
Maximum length in meters to limit voltage drop to 1V or less 5A 10A 20A
50A
80A
2.5
8.21 5.09 3.39 1.95 1.24
24.0 39.2 59.0
12
6
2.4
1.5 2.5 3.6 6.3
4 6
18.6 29.4 51.2
9.8
4
14.8 25.6
5.8
10 16 25 35
102.6 160.0 250.0 354.0
10.2
80
40 62 88
16
10
0.795 0.565
125 177
25.2 35.4
15.7
22
Table 3-3: Maximum wire length for 1V drop on lead (in meters)
For currents not shown in Table 3-2 and 3-3, use the formula: Maximum length=1000/(current x resistivity) Where current is expressed in amperes and resistivity in ohms/km or ohms/1000ft.
40
Made with FlippingBook Annual report maker