TRIGger:SOURce Selects the power supply input trigger source as follows: • BUS (*TRG & TRIG) and Front Panel • EXT Mainframe backplane Trigger IN PIN SCPI Command Syntax TRIGger[:STARt]:SOURce
7.12.12WAVE Subsystem This subsystem receives parameters to create a slopedwaveformof the output voltage or current. WAVE:COUNt Sets the number of times that the list is executed before it is completed. The command accepts parameters in the range 1 through 9999. Any number greater than 9999 is interpreted as INFinity. Use INF if you wish to execute a list indefinitely.
SCPI Command Syntax
[SOURce]:WAVE:COUNt
Parameters
1 to 9999 | INFinity
*RST
1
Examples
WAVE:COUN 3 WAVE:COUN INF
Query Syntax
[SOURce]:WAVE:COUNt? (if count>9999 the response is INF)
Returned Parameters
WAVE:CURRent This command specifies the output current points in a waveform list. The current points are given in the command parameters, which are separated by commas.
SCPI Command Syntax
[SOURce]:WAVE:CURRent
Default Suffix
A
Examples
WAVE:CURR 2.5,3.0,3.5
up to 12 parameters
Query Syntax
WAVE:CURR?
Returned Parameters
WAVE:LOAD Loads Voltage or Current, Time, STEP parameter and counter values to a specific location in the memory defined by numbers <1..4>.
SCPI Command Syntax
[SOURce]WAVE:LOAD
Example
WAVE:LOAD 3
Query Syntax
none
Returned Parameters
1..4