LIST:VOLTage Specifies theoutput voltagepoints ina list.Thevoltagepoints aregiven in the commandparameters, which are separated by commas.

SCPI Command Syntax

[SOURce]:LIST:VOLTage {,}

Default Suffix

V

Examples

LIST:VOLT 2.0,2.5,3.0 LIST:VOLT MAX,2.5,MIN

up to 12 parameters

Query Syntax

LIST:VOLT? 2.0,2.5,3.0

Returned Parameters

LIST:STORe Saves data under specified numbers <1..4> of the last LIST typed (voltage or/and current, dwell time, STEP parameter and counter).

SCPI Command Syntax

[SOURce]LIST:STORe

Example

LIST:STORe 3

7.12.9 STATus Subsystem Refer to Fig. 9-1 for more details. STATus:OPERation:EVENt?

This query returns the value of the Event register. This is a read-only register that receives data from the Condition register according to Enable register setting. Reading the Event register clears it.

SCPI Command Syntax GEN Command Syntax

STATus:OPERation:EVENt?

SEVE? None

Parameters

Returned Parameters

(Register Value) decimal

Examples

STAT:OPER:EVEN?

STATus:OPERation:CONDition? Returns the value of the Condition register, which is a read-only register that holds the real-time (unlatched) operational status of the power supply.

SCPI Command Syntax GEN Command Syntax

STATus:OPERation:CONDition?

STAT? None

Parameters

Returned Parameters

(Register Value) decimal

Examples

STAT:OPER:COND?