Air discharge
126
The pipe faces downward to avoid intake of foreign
Drainage outlet of drain pump משאבת מים מובנת
Vertical condensate pipe
Method to discharge water with the drain pump:
Air discharge
The pipe faces
Pipe fixture clamp
downward to avoid intake of foreign matters.
500~1000
500~1000
The drainage pipe should have a slope of 1/100 or
Ceiling
The net height of the
drainage pipe ≤ 1200
Natural drainage outlet Vertical condensate pipe
Water pump suction
Water outlet pipe of drain pump [ Caution ] Requirements for slope of the drainage pipe:
① The branch pipes of the drainage pipe shall have a slope of at least 1% that follows the direction of water flow. Lifting bolts shall be placed every 1–1.5m at a horizontal pipe and every 1.5–2.0m at a vertical pipe. Each vertical pipe shall have at least two fixing points for branch pipes and lifting bolts. ② Adverse slopes are prohibited, and no water may accumulate in the elbow pipe. The outlet end shall not be immersed in liquid.
Drainage plug
36
Installation
Natural drainage outlet
(Only applicable to models with water pumps)