ELECTRA | FAN COILS CATALOG 2024
Technical Data
EWC 09
EWC 12
EWC 18
EWC 30 S2 / S3 / S4 **
EWC AC motor
S2 / S3 / S4 **
S2 / S3 / S4 **
S2 / S3 / S4 **
Capacities - 2 pipes
Total cooling capacity
kW
1.54/1.76/2.35
1.88/2.86/3.96 1.41/2.16/3.01
2.78/3.46/4.65 2.10/2.64/3.57
3.69/5.44/7.16 2.66/4.03/5.37
Sensible capacity
kW 1.28/1.46/1.95
Cooling (1)
l/h
265/303/404
323/493/683
478/597/801
636/937/1233
Water pressure drop
kPa
5.5/6.8/10.9
4.4/8.5/14.4
7.8/11.2/18.3
4.2/7.5/11.5
Heating capacity
kW 1.92/2.17/2.74
1.94/3.15/3.68
3.16/3.92/5.28
3.85/6.26/8.51
l/h
331/374/472
334/543/634
544/675/909
663/1078/1466
Heating (2)
Water pressure drop
kPa
6.4/7.7/10.9
4.5/9.3/11.8
7.8/10.8/17.4
4.3/8.9/14.4
Capacities - 4 pipes
Total cooling capacity
kW
1.35/1.50/1.97 1.18/1.36/1.84
1.99/2.70/3.35 1.49/2.11/2.62
2.54/3.27/3.97 2.04/2.55/3.20
2.96/4.94/6.60 2.31/3.78/5.08
Sensible capacity
kW
Cooling (1)
l/h
232/258/359
342/465/576
437/563/683
511/851/1137
Water pressure drop
kPa
7.5/8.9/13.6
5.2/8.3/11.6
7.5/11.2/15.3
6.4/13.9/22.2
Heating capacity
kW 1.09/1.27/1.67
3.10/4.40/5.46
4.32/5.00/5.80
5.28/7.79/10.00
l/h
94/109/144
267/379/470
372/431/500
455/671/865
Heating (3)
Water pressure drop
kPa
15/19/30.2
8.1/14/19.9
13.9/17.6/22.5
4.7/8.2/12.1
Sound Levels - 2 pipes Sound power level Sound pressure level (4) Sound Levels - 4 pipes Sound power level Sound pressure level (4) NR (4)
dB(A) dB(A) dB(A) dB(A) dB(A) dB(A)
36/40/49 27/31/40 23/27/35 36/40/49 27/31/40 23/27/35
35/47/53 26/35/44 20/30/39 35/47/53 26/35/44 20/30/39
42/48/57 33/39/48 28/34/43 42/48/57 33/39/48 28/34/43
38/46/54 29/37/45 22/32/40 38/46/54 29/37/45 22/32/40
NR (4)
Fan Number
1
m³/h
360/450/659
320/504/734
486/626/900
500/824/1159
Filter
G1
Electrical Data Power supply
V/Ph/Hz
230V / 1~ / 50/60 Hz
Consumption - 2 pipes Consumption - 4 pipes Electrical heater Water Connections Type 2 pipes or 4 pipes “cooling”
W W
25/35/58 25/35/58
17/34/58 17/34/58
38/58/99 38/58/99
34/61/88 34/61/88
W
1380
2300
2300
2760
Female gas threaded
inch
3/4’’
3/4’’
3/4’’
1’’
4 pipes “heating”
inch
1/2’’
1/2’’
1/2’’
3/4’’
Weight and Dimensions Weight (without valve)
kg
14.8
16.5
16.5
37.1
** Standard factory set speeds with SysLogic controller. 1 According to Eurovent standard. Air: 27°C DB/19°C WB, Water in/out: 7°C/12°C.
2 According to Eurovent standard. Air: 20°C, Water in/out: 45°C/40°C. 3 According to Eurovent standard. Air: 20°C, Water in/out: 65°C/55°C. 4 Information data considering an hypothetical sound attenuation of the room and installation of -9 dB(A).
81
88
Made with FlippingBook - Online Brochure Maker