ELECTRA | FAN COILS CATALOG 2024
FCR 600
Cooling capacity Based on 26.7ºC (80ºF)/19.4ºC (67ºF) Entering air dry/Wet bulb temperatures
3 ROW COIL
4 ROW COIL
EWT WTR TH SH WF
PD TH SH WF
PD
ºC ºC kw kw m3/h m kw kw m3/h m (ºF) (ºF) (gpm) (ft) (gpm) (ft) (kbtuh) (kbtuh) (kbtuh) (kbtuh)
4.5 7.4
5.5 1.46 7.92 8.6
6.5 1.66 5.52
(8)
(25.20) (18.90) (6.30)
(26.0) (29.48) (22.11) (7.32)
(18.1)
5.6 (42)
5.5 7.3
5.5 1.14 4.6
8.5
6.4 1.33 3.63
(10) (25.00) (18.75) (5.00)
(15.1) (29.20) (21.90) (5.85)
(11.9)
6.7 6.9
5.1 0.89 2.96 7.9
5.9 1.02 2.29
(12) (23.40) (17.55) (3.90)
(9.7)
(26.94) (20.20) (4.49)
(7.5)
4.5 7.0
5.3 1.36 6.52 8.2
6.2 1.59 4.94
(8)
(24.00) (18.00) (6.00)
(21.4) (28.00) (21.00) (7.00)
(16.2)
7.2 (45)
5.5 6.7
5.0 1.04 3.9
7.9
5.9 1.22 3.14
(10) (22.95) (17.21) (4.54)
(12.8) (26.85) (20.14) (5.37)
(10.3)
6.7 6.2
4.6 0.79 2.38 7.1
5.3 0.91 1.83
(12) (21.00) (15.75)
(3.5)
(7.8)
(24.06) (18.04) (4.01)
(6.0)
4.5 6.1
4.6 1.19 4.94 7.2
5.4 1.39 3.93
(8)
(20.87) (15.65) (5.22)
(16.2) (24.52) (18.39) (6.13)
(12.9)
8.9 (48)
5.5 5.8
4.4
0.9
2.9
6.8
5.1 1.05 2.32
(10) (19.80) (14.85) (3.96)
(9.5)
(23.15) (17.36) (4.63)
(7.6)
6.7 4.7
3.5 0.61 1.49 5.4
4.0 0.69 1.13
(12) (16.00) (12.00) (2.67)
(4.9)
(18.36) (13.77) (3.03)
(3.7)
Heating Capacity Based on 21.1ºC (70ºF) Entering air Temperatures
1 ROW (1)
3 ROW COIL 4 ROW COIL EWT WF CAP PD WF CAP PD WF CAP PD ºC m3/h kw m m3/h kw m m3/h kw m (ºF) (gpm) (ft) (gpm) (ft) (gpm) (ft) 0.11 2.56 0.54 0.45 5.55 0.71 0.91 6.9 1.49 (0.5) (8.74) (1.76) (2.0) (18.93) (2.34) (4.0) (23.56) (4.88) (kbtuh) (kbtuh) (kbtuh) 0.23 2.68 1.49 0.68 5.97 1.49 1.14 7.01 2.26 (1.0) (9.15) (4.88) (3.0) (20.36) (4.88) (5.0) (23.91) (7.4) 0.34 2.82 2.98 0.91 6.18 2.44 1.36 7.08 2.99 (1.5) (9.61) (9.77) (4.0) (21.09) (8.01) (6.0) (24.17) (9.8) 0.11 3.64 0.52 0.45 7.89 0.69 0.91 9.82 1.44 (0.5) (12.43) (1.69) (2.0) (26.92) (2.26) (4.0) (33.51) (4.71) 0.23 3.81 1.43 0.68 8.49 1.44 1.14 9.96 2.24 (1.0) (13.01) (4.7) (3.0) (28.96) (4.71) (5.0) (34.01) (7.34) 0.34 4.01 2.87 0.91 8.79 2.35 1.36 10.07 2.87 (1.5) (13.67) (9.42) (4.0) (30.0) (7.72) (6.0) (34.38) (9.42) 0.11 4.67 0.5 0.45 10.11 0.66 0.91 12.58 1.38 (0.5) (15.93) (1.63) (2.0) (34.49) (2.17) (4.0) (42.93) (4.53) 0.23 4.88 1.38 0.68 10.87 1.38 1.14 12.77 2.15 (1.0) (16.67) (4.53) (3.0) (37.1) (4.53) (5.0) (43.6) (7.07) 0.34 5.13 2.87 0.91 11.26 2.26 1.36 12.91 2.76 (1.5) (17.52) (9.42) (4.0) (38.44) (7.4) (6.0) (44.05) (9.06) 0.11 5.69 0.48 0.45 12.33 0.64 0.91 15.34 1.33 (0.5) (19.42) (1.56) (2.0) (42.06) (2.09) (4.0) (52.36) (4.35) 0.23 5.96 1.33 0.68 13.26 1.33 1.14 15.57 2.07 (1.0) (20.33) (4.35) (3.0) (45.25) (4.35) (5.0) (53.14) (6.79) 0.34 6.26 2.65 0.91 13.73 2.18 1.36 15.74 2.65 (1.5) (21.36) (8.70) (4.0) (46.87) (7.14) (6.0) (53.72) (8.7) 60 (140) 71 (160) 82 (180) 49 (120)
(1) in a 1 row heating coil + 3 row cooling coil
- PD Water Pressure Drop in m (ft) of water kbtuh - Thousands btu's per hour
EWT - Entering Water Temperature WTR - Water Temperature Rise
WF -
TH - Total Heat SH - Sensible Heat
Water Flow
CAP- Unit Heating Capacity
86
79